Obiat Pty Ltd distributors of Electronic and Professional Scientific Test Equipment.

 

Sydney Australia

. . . . keeping your world up and running

Navigation: Current Measurement Probes > Leakage Current Meters and Probes Index > Model AN-1
 
 
 

The Artificial Neutral Model AN-1 generates a momentary grounded artificial neutral to allow the measurement of fault currents on ungrounded three-phase systems.

The Artificial Neutral is grounded intermittently through a relay driven by an internal electronic timer. This periodic grounding technique performs three functions – limits the possibility of insulation faults within the instrument, allows for better discrimination of actual fault current and limits instrument overheating.

Relay closure time is switch selectable, Fast (0.5 seconds) or Slow (2.3 seconds), so that the ground fault clamp can be used on a meter with either an analog or digital display. An internal buzzer, also driven by the relay, is activated each time the neutral connection is grounded. Three LEDs, one for each phase, show the presence of each of the three phases prior to measurement. A fourth green LED indicates that the instrument is operating.
 









 
  • Designed for ungrounded networks — provides intermittent path to ground for leakage current measurements.
  • Works from 30 to 600VAC.
  • Red LED phase fault indicator.
  • Switch selectable ground fault cycling of 500mS or 2.3 seconds.
  • Buzzer alerts each momentary fault.
  • Battery operated.
  • Double insulated, fire retardant case.
  • Four color-coded 5 ft 1000V rated leads supplied with alligator clips.
  • Works with Model 2620 and other leakage current probes.

  • Troubleshoot faulty three-phase ungrounded devices.
  • Assist in leakage current measurements on ungrounded systems.
  • Create momentary ground conditions to detect fault currents.

Typical Points for Measuring Leakage Current
 

Construction

On ungrounded networks, the Model AN-1 generates a momentary grounded artificial neutral. Leakage current measurements can then be made, using a leakage current clamp and a multimeter, between the Model AN-1 and the load.

 
 
Working voltage 30 Volts to 600 Volts
Frequency 45Hz to 65Hz
Resistance Per Phase 3.9kΩ ±5%
Relay Duty Cycle
  Slow
  Fast
 
500mS
2.3 seconds
Power Source Eight 1.5 volt type 'AA' batteries
 
 
Dimensions 220mm x 136mm x 150mm
(8.7" x 5.4" x 5.9")
Weight 1.3kg (2.9lbs)
Case Fire resistant polycarbonate UL94 VO
Protection Index IP20
 
 
 
Operating Temperature
 
0° to 50°C (32°F to 122°F)
10 to 90% RH (non-condensing)
Storage Temperature
 
-40° to 70°C (-40°F to 158°F)
10 to 90% RH (non-condensing)
 
 
 
Safety Rating 600V CAT III
Double Insulation Yes
CE Mark Yes
 
 
 
 
Catalog No. 1971.01 Artificial Neutral Model AN-1
 
 
 
 
Catalog No. 2125.52 AC Leakage Current Probe Model 2620

 

AEMC | AMPROBE | CIE | FLUKE | HT ITALIA | HODEN | PROVA | POMONA | RAYTECH |  SILVERTRONIC
Home | PRODUCTS | SEARCH
Obiat Pty. Ltd.
A.C.N. 003 166 952      A.B.N. 23 003 166 952
Unit 9A/8 Avenue of the Americas, Newington NSW 2127 Australia
P.O. Box 6901 Silverwater  NSW Australia 1811

Phone: 61-2-9748- 8699

Fax: 61-2-9748-8544

E-mail:
 

 information@obiat.com.au
sales@obiat.com.au

Copyright ©                                             Last Update: Wednesday, 13 April 2011