The Artificial Neutral Model AN-1 generates a momentary grounded
artificial neutral to allow the measurement of fault currents on
ungrounded three-phase systems.
The Artificial Neutral is grounded intermittently through a relay
driven by an internal electronic timer. This periodic grounding
technique performs three functions – limits the possibility of
insulation faults within the instrument, allows for better
discrimination of actual fault current and limits instrument
overheating.
Relay closure time is switch selectable, Fast (0.5 seconds) or Slow
(2.3 seconds), so that the ground fault clamp can be used on a meter
with either an analog or digital display. An internal buzzer, also
driven by the relay, is activated each time the neutral connection
is grounded. Three LEDs, one for each phase, show the presence of
each of the three phases prior to measurement. A fourth green LED
indicates that the instrument is operating.
|
|
|
|
|
Typical Points for Measuring Leakage Current
|
 |
Construction |
|
 |
|
On ungrounded networks, the Model
AN-1 generates a momentary grounded artificial neutral. Leakage
current measurements can then be made, using a leakage current clamp
and a multimeter, between the Model AN-1 and the load. |
|
| |
 |
| |
| Working voltage |
30 Volts to 600
Volts |
| Frequency |
45Hz to 65Hz |
| Resistance Per Phase |
3.9kΩ
±5% |
| Relay Duty Cycle |
| |
Slow |
| |
Fast |
|
|
| Power Source |
Eight 1.5 volt
type 'AA' batteries |
|
| |
 |
| |
| Dimensions |
220mm x 136mm x
150mm
(8.7" x 5.4" x 5.9") |
| Weight |
1.3kg (2.9lbs) |
| Case |
Fire resistant
polycarbonate UL94 VO |
| Protection Index |
IP20 |
|
| |
| |
 |
| |
Operating Temperature
|
0°
to 50°C (32°F
to 122°F)
10 to 90% RH (non-condensing) |
Storage Temperature
|
-40°
to 70°C (-40°F
to 158°F)
10 to 90% RH (non-condensing) |
|
| |
| |
 |
| |
| Safety Rating |
600V CAT III |
| Double Insulation |
Yes |
| CE Mark |
Yes |
|
| |
| |
| |
 |
| |
| Catalog No. 1971.01 |
Artificial Neutral Model AN-1 |
|
| |
| |
| |
 |
| |
| Catalog No. 2125.52 |
AC Leakage Current Probe Model
2620 |
|