The Clamp-On Harmonic Meter Model F25
is a portable, battery operated power quality instrument. The Model
F25 performs current and voltage measurement in True RMS as well as
current and voltage in DC, and immediate readings of Total Harmonic
Distortion (%THD), Individual harmonic orders through the 25th,
Distortion Factor (%DF), Crest Factor (CF) and Peak of distorted
currents and complex voltages. Displays Min, Max, and Average
measurement values allowing recording for over 24 hours with an
internal clock logging record time. Frequency (Hz) can be measured
through either the current or the voltage. The slim clamp-on style
makes it easy to work around crowded breaker panels and
transformers.
|
|
 |

- Designed for traditional and nonlinear loads.
- Simple clamp-on operation with power quality features.
- Accurate TRMS amps or volts (AC or AC + DC).
- Accurate DC measurements ( A or V).
- Recording mode stores: min, max, avg, max & peak.
- Direct reading of %THD, %DF, CF and Peak (+ or -).
- Display individual harmonic orders DC to 25th in A or V.
- Smooth function for stable readings.
- Auto or manual ranging.
- Peak measurements (AC or DC)(+ or -).
- K factor for proper transformer sizing.
- Percent ripple for DC.
- Transformer Harmonic Derating Factor (THDF).
- Frequency measurements in A or V.
- Auto-off feature.
- 31-segment analog bargraph.
- Low battery indicator.
- Battery voltage level check.
- Rugged Lexan construction.
- Audible control/warning indications.
- Built to UL, CSA, GS, VDE and IEC 1010 safety standards.
- Triple display.
|
|

- True RMS and DC voltage and current measurements.
- Determine levels of voltage and current distortion.
- Identify harmonic distortion patterns and sources of voltage
harmonics.
- Locate sources of harmonic current.
- Measure individual harmonics.
- Identify nonlinear loads.
- Prevent overheating in electrical distribution equipment, false
circuit breaker tripping.
- Power factor correction capacitor failure.
- Locate overloaded neutral wires.
- Derate transformers and generators to prevent overheating.
- Measure crest factor to evaluate harmonic content and determine
CBEMA derating factor.
Model
F25 Datasheet PDF (167kb) |
|
| |
| |
 |
| |
|
AC Current (True RMS) |
| 0.3 to 1000Arms |
| ±0.5 to ±1500A pk |
|
|
AC Voltage (True RMS)
|
|
Input Range: |
0.05 to 600Vrms, |
| |
±0.05 to ±1500V pk |
|
Crest Factor: |
>5 below 300V |
|
Input Impedance: |
1MΩ |
|
|
DC Current |
±0.03 to ±1500A |
|
DC Voltage |
±0.05 to ±600V |
|
Total Harmonic Distortion (%THD) |
0.2% to 1000% (to RMS or Fund) |
|
Distortion Factor (%DF) |
0.2% to 100% |
|
Individual Harmonics |
0.2% to 300% (%THD or %DF) |
|
Transformer Harmonic Derating Factor (CBEMA
THDF) |
0.10 to 1.00
|
|
Transformer K Factor Rating |
1 to 30 |
|
Frequency (Hz) |
0.5 to 20,000Hz |
|
Jaw Opening |
1.7" (43mm) |
|
Conductor Size |
|
Cable: |
1.97" (50mm) |
|
2 Busbars: |
1.97" x 0.20" (50mm x 5mm) |
|
1 Busbar: |
3.15" x 0.20" (80mm x 5mm) |
|
|
| |
| |
| |
 |
| |
|
Catalog Number |
Description |
|
2111.39 |
Model F25 Clamp-on Harmonic Meter
(TRMS, 600VAC and 1500AAC/DC) |
|
|