| Specifications |
|
True RMS |
True RMS sensing |
|
AC Voltage |
600.0V |
|
AC Voltage Basic
Accuracy |
±(0.5% of reading + 5 digits) at 50/60Hz |
|
AC Current |
40.0A, 400.0A, 1000A |
|
AC Current Basic
Accuracy |
±(1.0% of reading + 5 digits) at 50/60Hz |
|
|
|
|
DC Voltage |
600.0V |
|
DC Voltage Basic
Accuracy |
±(0.5% of reading + 5 digits) |
|
|
|
|
Resistance |
999.9 Ohms |
|
Resistance Basic
Accuracy |
±(1.0% of reading + 6 digits) |
|
Frequency |
5.00Hz to 500Hz |
|
Frequency Basis
Accuracy |
±(0.5% of reading + 4 digits) |
|
|
|
|
Active Power (W) |
0 to 600.0 kW |
|
Active Power (W)
Basic Accuracy |
±(2.0% of rdg + 6 digits) at Harmonics Fund to 10th and
PF>0.7 |
|
Reactive Power
(VAR) |
0 to 600.0 kVAR |
|
Reactive Power
(VAR) Basic Accuracy |
±(2.0% of rdg + 6 digits) at Harmonics Fund to 10th and
PF>0.7 |
|
Apparent Power
(VA) |
0 to 600.0 kVA |
|
Apparent Power
(VA) Basic Accuracy |
±(2.0% of rdg + 6 digits) at Harmonics Fund to 10th |
|
|
|
|
Power Factor |
0.10 to 0.99 |
|
Power Factor Basic
Accuracy |
±3 digits at Harmonics Fund to 21th |
|
|
|
|
Temperature |
-50°C
to 300°C (-58°F
to 572°F) |
|
Temperature Basic
Accuracy |
±(2.0% of Rdg + 3°C), ±(2.0% of Rdg + 6°F) |
|
|
|
|
Sampling Rate
|
1 per second (Power
Function) |
|
|
4 per second
(Voltage, ACA clamp-on, Hz and Temp Functions) |
|
Polarity |
Automatic |
|
Low Battery |
Below 2.4V approx. |
|
Transient
Protection |
6.5kV (1.2/50μs
surge) |
|
Pollution |
Degree 2 |
|
E.M.C. |
Meets EN61326 (1997,
1998/A1), EN61000-4-2 (1995), and |
|
|
EN61000-4-3 (1996) an
RF field of 3V/m: |
|
|
Specified Accuracy +
45 digits |
|
|
performance above
3V/m is not specified |
| |
| General Specifications |
|
Operating
Temperature |
0°C
to 40°C |
|
Storage
Temperature |
-20°C
to 60°C, <80% R.H. (battery removed)
|
|
Power Supply |
Standard 1.5V 'AAA'
size (NEDA 24A or IEC LR03) battery x 2 |
|
Power Consumption |
10mA typical
(Voltage, ACA, Hz and Power Functions) |
|
|
4mA typical (HM and
Temperature functions) |
|
Size |
224mm (L) x 78mm (W)
x 40mm (D) |
|
Weight |
224g approx |
| |
|
|
Included Accessories |
|
Users Manual, Batteries,
Thermocouple, Carrying Case and
Test Leads |
| |
| Optional Accessory |
|
Communication Accessory |
RS-232 KIT2 Data recording System |
| |
|
| |
|