Model ACD-56HPQ
400A Power Quality Clamp-On Meter
 
Amprobe Model ACD-56HPQ Power Quality Clamp-On Meter Features
  • TRMS Measurements.
  • AC Current up to 400A.
  • AC/DC Voltage up to 600V.
  • Active, Reactive and Apparent Power Single/Three Phase.
  • Power Factor, Cos Ø Single/Three Phase/Energy.
  • Frequency (with test leads and Jaw)
  • Phase sequence with single wire (patented)
  • Resistance, and Capacitance.
  • Audible Continuity.
  • Auto and Manual ranging.
  • Auto-check feature automatically selects DCV, ACV or Resistance.
  • Auto Power OFF.
  • Backlight Screen.
  • Data Hold.
  • Min/Max/Avg recording.
  • Peak function (Fast 1ms).
  • Low battery indication.
  • Voltage and Current Harmonics up to 25th with THD%.
  • Maximum conductors 45mm (1.77").

Safety conformity

Model ACD-56 HPQ Specifications (PDF)
(documents in PDF format and will open in a new window)
 

Specifications

AC Voltage

1.6V to 599.9V

AC Voltage Basic Accuracy

±(1.0% of Rdg + 3 digits)

AC Current

0.0A to 399.9A

AC Current Basic Accuracy

±(1.0% of Rdg + 3 digits)

AC Peak Current (at 1ms response time)

10A to 800A

AC Peak Current Basic Accuracy

±(5.0% of Rdg + 10 digits)

 

 

DC Voltage

1.6V to 599.9V

DC Voltage Basic Accuracy

±(1.0% of Rdg + 3 digits)

 

 

Resistance

0 to 499.9Ω, 999Ω, 1999Ω

Resistance Accuracy

±(1.0% of Rdg + 5 digits)

Frequency (with test leads/Jaw)

40.0Hz to 399.9Hz

Frequency Basic Accuracy

±(0.5% of Rdg + 1 digits)

 

 

Voltage/Current Harmonics

THD, Individual harmonics 1 to 25 Harmonics

 

1 to 16 at ±(10.0% of Rdg + 5 digits)

Power

Active, Reactive and Apparent

Power Factor, Cos Ø

0.20 to 1.00

Power Factor Basic Accuracy

±(2.0% of Rdg + 2 digits)

 

 

Safety Standards

EN61010, Class 2, double reinforced insulation

 

Pollution Level 2

 

Over Voltage CAT III 600V between terminals and ground

EMC

This apparatus was designed in accordance with EMC std's

 

in force and its compatibility has been tested in accordance

 

with EN61326 (1997) + A1 (1998) + A2 (2001)

Reference Temperature

23°C ±5°C

Operating Temperature

5°C to 40°C

   
   

 

 

General Specifications

Power Supply

2 type 'AAA' 1.5V batteries

Battery Life

About 90 hours of continued measurement

Low Battery indication

Symbol is displayed when battery level is too low

Display

4 digit LCD with maximum reading 9999 units plus

 

decimal point and sign

Sample Rate

64 samples in 20ms

Conversion Mode

True RMS

Size

205mm (L) x 64mm (W) x 39mm (D)

Weight

280g approx.

Jaws Opening

30mm

Maximum Conductor Size

30mm
   

Included Accessories

Users Manual, Batteries, Rubber Holster, Carrying Case and Test Leads

 

 

AEMC | AMPROBE | CIE | FLUKE | HT ITALIA | HODEN | PROVA | POMONA | RAYTECH |  SILVERTRONIC
Home | PRODUCTS | SEARCH
Obiat Pty. Ltd.
A.C.N. 003 166 952      A.B.N. 23 003 166 952