Model AMB-5KVD
MEGATEST 5000 Insulation Tester |
| |
|
The AMB-5KVD "MEGATEST 5000" is for demanding
and professional clients who are looking for increasingly
accurate insulation measurements. It provides flexible measuring,
easy programming and accuracy. It can measure up to 5000 volts while
keeping control of every factor involved (insulation resistance,
voltage and measuring time).
|
 |
Features
- Tests insulation of wires, cables, transformers, electrical
motors and generators.
- Comes as a complete kit including test leads and PC software.
- Built in automatic voltmeter up to 5000V warns against
hazardous energized systems.
- Programmable setups of test voltages and timers.
- Performs the dielectric absorption ratio test.
- One testing instrument for low and high voltage systems.
- Internal memory, measurements can be stored for future
reference.
- Data download to PC.
- Rugged, durable case.
 |
|
| Specifications (23°C ±1°) <75%
R.H. |
| Range |
Accuracy |
| 100V to 500V |
500V to 1000V |
1000V to 2500V |
2500V to 5000V |
| 100 KΩ to 500
KΩ |
±(20% Rdg + 10
dgt) |
±(20% Rdg + 10
dgt) |
±(20% Rdg + 10
dgt) |
±(20% Rdg + 10
dgt) |
| 500 KΩ to 50
GΩ |
±(5% Rdg + 1
dgt) |
±(5% Rdg + 1
dgt) |
±(5% Rdg + 1
dgt) |
±(5% Rdg + 1
dgt) |
| 50 GΩ to 100
GΩ |
±(20% Rdg + 10
dgt) |
±(5% Rdg + 1
dgt) |
±(5% Rdg + 1
dgt) |
±(5% Rdg + 1
dgt) |
| 100 GΩ to 250
GΩ |
---- |
±(20% Rdg + 10
dgt) |
±(5% Rdg + 1
dgt) |
±(5% Rdg + 1
dgt) |
| 250 GΩ to 500
GΩ |
---- |
---- |
±(20% Rdg + 10
dgt) |
±(5% Rdg + 1
dgt) |
|
Minimum Resistance Resolution: 1%
Voltage Indication Resolution: 1.22V |
| |
| Current (which can be delivered) |
| Voltage Setting |
Maximum Current |
| 100V to 500V |
3.00mA |
| 1000V to 5000V |
1.40mA |
|
The output current is automatically limited |
| |
| Voltage Measurement |
| Voltage Range |
Resolution |
Accuracy |
| 0V to 500V |
1.22V |
±(10% of Rdg +
10 digits) |
| 500V to 5000V |
1.22V |
±(10% of Rdg + 5
digits) |
|
The limits shown here are valid both DC of any polarity and for AC
Discharge time at 5000V: <1.5s x µF |
| |
| Safety |
| Instrument According to Standard: |
EN 61010-1 |
| Insulation: |
Class 2, Double insulation |
| Pollution Level: |
2 |
| Over-Voltage Category: |
CAT III 600V |
| Serial Port Insulation: |
25mm (max. 5000V) |
|
| |
| |
| General Specifications |
| Display |
LCD 1-unit 3 digits, 2-units 4 digits, bargraph 32 segments, |
| |
plus other symbols |
| Display Update Rate: |
2/sec. |
| Measurement Method: |
Volt-ampero-metric system |
| Parameter Memory: |
20 different parameters |
| Stored Measurements: |
200 measurements with their parameters and results |
| Operating Temperature: |
23°C to 40°C (41°F to 104°F) <80%
R.H. |
| Storage Temperature: |
-10°C to 60°C (14°F to 140°F) <70%
R.H. |
| Noise Level: |
<40dB |
| EMC: |
Tested to EN 50081-1, EN 50082-1 |
| Power Supply: |
4 each, 1.5 volt, size 'D' Alkaline |
| Automatic Turn Off: |
Turns Off after 10 minutes without use |
| Dimensions: |
290mm (L) x 340mm (W) x 145mm (H) |
| |
11.5" (L) x 13" (W) x 5.75" (H) |
| Weight: |
4kg (8.8 lb) |
|
| |
| |
|
Included Accessories |
|
Three Test Leads with safety
boot and an alligator clip, Serial cable and CD-ROM with "SUPERLINK"