Model AT- 4003 CON Advanced Wire Tracer |
| |
|
Amprobe's reputation for out-performing circuit
tracers has just gotten better. These new and improved advanced
tracers combine features and functions to make your job easier.
The Model AT-4003
CON contains: R-4000 CON
Receiver, T-4000 Transmitter (9V-600V), C2901 Cordset, C2902
Cordset, MTL-G Grounding Test Lead with Alligator Clip, Hard Carrying Case and User's Manual.
|
|
 |
Features
- Extremely easy to use.
- One universal transmitter - automatically switches to work
with either energized or non-energized systems.
- Receiver is not position sensitive - does not need to be
rotated in order to provide accurate readings.
- Traces live wires buried or hidden behind walls.
- Traces energized and non-energized (open, broken) wires.
- Performs tests without having to interrupt power.
- Locates breakers, neutral and ground lines.
- Locates and traces wires in walls, floors, conduit, computer
cables etc.
- Pinpoints shorts, ground faults and broken wires.
- Does not interfere with sensitive electronic equipment.
- Precise sensitivity adjustment.
- Optional Battery Booster strengthens signal for open
tracing.
- Optional Clamp-on attachment injects signal for non-contact
operation.
Wire Tracer Model and Equipment Guide
|
|
|
General Specifications |
|
Operating Temperature |
-18°C to 49°C (0°F
to 120°F) |
|
Storage Temperature |
-40°C to 66°C
(-40°F to 150°F) |
|
Case Material |
ABS |
|
Case Size |
14mm x 7mm |
|
| |
| |
|
Receiver Specifications
(R4000 CON) |
|
Detectors |
Electromagnetic coil pickup for short
mode: electrostatic plate for open mode. |
|
Sensitivity |
Low and High programmable gain from
traced wire. |
|
Short Mode Performance |
Over 20 feet in air under test
conditions. |
|
Open Mode Performance |
Over 12 feet in air under test
conditions |
|
50Hz,60Hz, and 400Hz Rejection |
120dB |
|
Power |
9 volt battery, IEC 6LR61 |
|
Display |
10 LED's with chroma filter lens |
|
Case |
ABS 911 (flame retardant) |
|
Weight |
113 gms |
|
|
|
|
Transmitter
Specifications (T-4000) |
|
Operating Voltage |
9V to 600V AC or DC |
|
Operating Frequency |
32.768KHz |
|
Display |
Liquid Crystal Display (LCD) |
|
Duty Cycle |
Transmits 2 pulses with a duration of
0.0625 each, every 0.5 seconds. |
|
Current Output of Signal |
Low Mode: 30mA peak, 11mA average
Medium Mode: 36mA peak, 12mA average
High Mode: 63mA peak, 13mA average |
|
Fuse |
Fast acting 250mA at 1000V (6mm x 46mm)
(P/N: FA6X46MM) |
|
Battery Power |
9 Volt Alkaline battery, IEC 6LR61
(Optional Battery Accessories B2024 or B2025) |
|
Case Material |
ABS |
|
Weight |
143.5gms |
|
| |
| |
|
Optional Clamp-on Transmitter
Accessory (A2202) |
|
Operating Frequency |
32.768KHz as supplied by T-4000 |
|
Maximum Wire Size |
2000 MCM or 2-inch dia. cable |
|
Power |
Power is supplied by T-4000 |
|
Case Breakdown Voltage |
3000 Volts |
|
| |
| |
|
Optional Battery Pack
Accessory (B2024) |
|
Battery Type |
Nickel-Cadmium rechargeable (20 x type
'AA' cells) |
|
Capacity |
24-volt, 600mA/h |
|
Rechargeable Time |
14 hours |
|
Protection |
Internal self-resetting fuse |
|
| |
| |
|
Optional Charger Accessory (B2025) |
|
Input Voltage |
115 Volts AC 50/60Hz |
|
Output Voltage |
24-volt, 350mA/h |
|
| |
| |