Obiat Pty Ltd distributors of Electronic and Professional Scientific Test Equipment.

 

Sydney Australia

. . . . keeping your world up and running

Navigation: Amprobe Power Quality Product Index > Model DM-II PRO
Amprobe Test Instruments Logo Amprobe Power Quality Instruments
Model DM-II Power Quality Data Logger
 
Amprobe DM-II PRO Power Quality Recorder/Data-logger Features
  • Comes as a complete kit, CT’s and PC software are included with product
  • Works with single and three phase systems (Y and delta)
  • Capable of recording all parameters (single or three phase) simultaneously
  • All readings are True RMS (TRMS)
  • User selectable rates allow recording from one hour to several months
  • Five built-in selectable languages: English, Spanish, French, German and Italian
  • Readings and charts can be viewed on the DM-II LCD screen or downloaded to a PC
  • Intuitive, very easy to use, Windows compatible PC software
  • Line or battery powered

Specifications

AC Voltage Range

0 to 600V

AC Voltage Accuracy

±(1% of Rdg + 3 digits)

 

 

AC Current Range

1A to 1000A (expandable to 3000A with optional CT's)

AC Current Accuracy

±(1% of Rdg + 3 digits)

 

 

Power

Working (W), Reactive (R), and Apparent (VA)

Power Factor

0.00 to 1.00

Energy

kWh

Peak Demand

kW

Fundamental Frequency

50Hz/60Hz

Available Recording Time

1 hour to several months depending on set-up

Recording Modes/Rates/Intervals

User selectable normal and loop (wrap around) recording

 

modes, user selectable recording rates of 1sec, 5 sec,

 

15 sec, 30 sec, 1 min, 5 min, 15 min, and 30 minutes.

 

User selectable recording intervals of none, 15 min and 30 min.

Memory

Total of 600K RAM memory. The memory has a back-up

 

lithium battery to preserve its contents in the absence of

 

power.

Real Time Clock

User programmable, displayed in 12/24 hour format and

 

HH:MM:SS, Day, Month Date, Year, and Daylight saving

 

option. Accuracy of ±1 min/mth

System Configuration

Total of four pre-stored set-up phase configurations for

 

1Ø and 1Ø systems: 1Ø 2W, 1Ø 3W, 3Ø 3W Straight

 

Delta, and 3Ø 4W Wye

Note: Any or all parameters of a phase configuration can be recorded

 

 

PC Interface

Optically isolated RS-232 serial interface. The DM-II

 

View PRO software for display, data analysis, and report

 

generation.

 

 

General Specifications

Safety Standards

Designed to meet UL 3111-1, CE (LVD/EMC/EMI)

Case Material

Injection moulded flame retardant ABS911, rugged,

 

water-resistant, and corrosion proof

Dimensions

17.5" (L) x 11.6" (W) x 7.5" (D)

Weight

16 lbs (7.3kgs) includes batteries, 4 CT's, voltage leads

 

and alligator clips)

Power Requirements

AC line voltage with battery back-up operation

Battery

Six Alkaline "D" cells (not supplied)

Battery Life

21 hours continuous with backlight 'OFF', 1 second

 

recording rate, normal recording mode, all parameters

 

selected for a 3Ø 4W Wye configuration

Operating Temperature

0°C to 50°C, Relative humidity <85%

Storage Temperature

-2C to 60C, Relative humidity <90%

 

 

Included Accessories

Instrument supplied as a complete kit, CT's and PC software,  and user manual

 
 
AEMC | AMPROBE | CIE | FLUKE | HT ITALIA | HODEN | PROVA | POMONA | RAYTECH |  SILVERTRONIC
Home | PRODUCTS | SEARCH
Obiat Pty. Ltd.
A.C.N. 003 166 952      A.B.N. 23 003 166 952
Unit 9A/8 Avenue of the Americas, Newington NSW 2127 Australia
P.O. Box 6901 Silverwater  NSW Australia 1811

Phone: 61-2-9748- 8699

Fax: 61-2-9748-8544

E-mail:
 

 information@obiat.com.au
sales@obiat.com.au

Copyright ©                                             Last Update: Tuesday, 19 July 2011