1650B Series Multifunction
Installation Testers - Specifications
 
Specifications
 
AC Voltage Measurement Range: 500 V
Resolution: 0.1 V
Accuracy (50 - 60 Hz) 0.8% + 3
Input Impedance 3.3 MW
Overload Protection 660 Vrms
Continuity Testing Range (autoranging): 20 W, 200 W, 2000 W
Resolution: 0.01 W, 0.1 W, 1 W
Test Current: > 200 mA
Open Circuit Voltage: > 4 V
Accuracy: ± (1.5%+3 digits)
Insulation Resistance Measurement Fluke 1651B
Test Voltage: 250 - 500 - 1000V

Fluke 1652

Test Voltage: 250 - 500 - 1000 V
Accuracy of Test Voltage:¹ +10% , -0%

Fluke 1653
Test Voltage: 50 - 100 - 250 - 500 - 1000 V

Test Voltage: 50 V
Test Current: 1 mA @ 50 kW
Insulation Range: 10 kW - 50 MW
Resolution: 0.01 MW
Accuracy: ± (3% + 3 digits)

Test Voltage: 100 V
Test Current: 1 mA @ 100 kW
Range/Resolution: 20 MΩ/0.01MΩ
Range/Resolution: 100 MΩ/0.1MΩ
Accuracy: ± (3% + 3 digits)


Test Voltage: 250 V
Test Current: 1 mA @ 250 kW
Range/Resolution: 20 MW/0.01 MW
Range/Resolution: 200 MW/0.01 MW

Accuracy: ± (1.5% + 3 digits)

Test Voltage: 500 V
Test Current: 1 mA @ 500 kW
Range/Resolution: 20 MW/0.01 MW
RangeResolution: 200 MW/0.01 MW

Accuracy: ± (1.5% + 3 digits)
RangeResolution:
500 MW/0.01 MW
Accuracy: 10%

Test Voltage: 1000 V
Test Current: 1 mA @ 1 MW
Range/Resolution: 20 MW/0.01 MW
Range/Resolution: 200 MW/0.01 MW

Accuracy: ± (1.5% + 3 digits)
Range/Resolution: 500 MW/0.01 MW

Accuracy: 10%

Auto Discharge: Discharge time constant, 0.5 second for C = 1 µF or less
Live Circuit Detection: Inhibits test if terminal voltage > 30 V prior to initiation of test
Maximum Capacitive Load: Operable with the 5 µF load
 
Loop Impedance Measurement (High Current Mode and Non-Trip Mode) Range: 100 - 500 VAC (50/60 Hz)
Input connection: Soft Key selection
Loop impedance: Phase to earth
Line impedance: Phase to neutral
Limit on consecutive tests: Automatic thermal shutdown after 50 consecutive tests at 10 second intervals (typical)

Max. Test Current High
Current Mode:
Non-Trip Mode:


Range: 20 W
Resolution: 0.01 W
Range: 200 W
Resolution: 0.1 W
Range: 2000 W
Resolution: 1 W
Accuracy (non-trip mode): ±(3% + 6 digits)
Accuracy (high current mode): ±(2% + 4 digits)

PFC, PSC Test Computation: PFC or PSC determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance
Range: 0 - 25 kA
Resolution (Ik < 1000 A): 1 A
Resolution (Ik >= 1000 A): 0.1 kA
Accuracy: Determined by accuracy of loop resistance and mains voltage measurements.
RCD Testing Note 1 Fluke 1651B:  AC, G, S
Fluke 1652B:  AC, G, S, A
Fluke 1653B:  AC, G, S, A
Tripping Time Test (ΔT) Trip Time Accuracy ±(1% Reading + 1 digit)

Multiplier: x ½
Current Settings: 10, 30, 100, 300, 500, 1000 mA
Current Accuracy: +0% - 10%
RCD Type: G Note 1
Measurement Range (EU): 310 ms
RCD Type: S Note 1
Measurement Range (EU): 510 ms
Measurement Range (UK): 2000 ms

Multiplier: x 1
Current Settings: 10, 30, 100, 300, 500, 1000 mA
Current Accuracy: +0% - 10%
RCD Type: G Note 1
Measurement Range: 310 ms
RCD Type: S Note 1
Measurement Range: 510 ms

Multiplier:
x 1
Current Settings: 10, 30 mA
Current Accuracy:
±10%
RCD Type: G Note 1
Measurement Range: 50 ms
RCD Type: S Note 1
Measurement Range: 160 ms

 
Tripping Current (ramp) Test - Fluke 1652B, Fluke 1653B Current Range: 50% - 110% of RCD's rated current
Step Size: 10% of IΔN
Dwell time (Type 1G): 300 ms / step
Dwell time (Type 1S): 500 ms / step
Trip Current Measurement Accuracy: ±5%
Earth Resistance Test (RE) - Fluke 1653B Range: 200 W
Resolution: 0.1 W
Accuracy: ±(2% + 5 digits)
Range: 2000 W
Resolution: 1 W
Accuracy: ±(3.5% + 10 digits)
Frequency: 128 Hz
Compliance Voltage: +25 V
Phase Sequence Indication - Fluke 1653B Icon: Icon Phase Sequence indicator is active
Display of Phase Sequence:
Displays ‘1-2-3’ in digital display field for correct sequence.
Displays ‘3-2-1’ for incorrect phase.
Dashes in place of a number indicate a valid determination could not be made.
RCD Types Note 1 G General, no delay
S Time delay
A Responds to pulsed signal
AC Responds to AC
 
 
Environmental Specifications
 
Operating Temperature -10 °C to 40 °C
Humidity
(Without Condensation)
10 to 30 °C: 95% RH
30 to 40 °C: 75% RH
 
 
Safety Rating
 
Safety Rating EN 61010-I CAT III 500 V
 
 
General Specifications
 
Size 10cm (L) x 25cm (W) x 12.5 cm (H)
Weight 1.17 kg
Batteries Type AA: 6
Warranty 3 years
Battery type Alkaline supplied, usable with 1.2V NiCD or NiMH rechargeable batteries


 

AEMC | AMPROBE | CIE | FLUKE | HT ITALIA | HODEN | PROVA | POMONA | RAYTECH |  SILVERTRONIC
Home | PRODUCTS | SEARCH
Obiat Pty. Ltd.
A.C.N. 003 166 952      A.B.N. 23 003 166 952
Unit 9A/8 Avenue of the Americas, Newington NSW 2127 Australia
P.O. Box 6901 Silverwater  NSW Australia 1811

Phone: 61-2-9748- 8699

Fax: 61-2-9748-8544

E-mail:
 

 information@obiat.com.au
sales@obiat.com.au

Copyright ©                                             Last Update: Wednesday, 13 April 2011