The perfect tool for tracking down single-phase
power -related problems The Fluke Model 43B Power Quality Analyzer performs the measurements you
need to maintain power systems, troubleshoot power problems and
diagnose equipment failures. The new Model 43B has 20 storage locations
and can store data as well as screens. |
|

|

- NiMH Battery provides extended operating time
of 6.5 hours.
- Combines the most useful capabilities of a
power quality analyzer, multimeter and oscilloscope.
- Calculates 3-phase power on balanced loads,
from a single-phase measurement.
- Trends voltage, current, frequency, power
harmonics and captures voltage sags, transients and inrush
current.
- Monitoring functions help track intermittent
problems and power system performance.
- Records two selectable parameters for up to 16
days.
- 20 measurement memories to save/recall screens
and data with cursor readings.
- FlukeView® software can log harmonics and all
other readings over time and provides a complete harmonics profile
up to the 51st harmonic.
- Measures resistance, diode voltage drop,
continuity, and capacitance.
- User/applications manual and power quality
video to help answer tough questions.
- Complete package with voltage probes and 400A
current clamp, FlukeView Software and optically isolated interface
cable.
- 3-year warranty on the 43B and 1-year on the
accessories.
Model 43B Datasheet PDF (197kb)
|
|
|
 |
Harmonics
- Voltage, current and power harmonics up to 51st.
- Total harmonic distortion (THD)
- Phase angle of individual harmonics.
|
| |
|
|

|
Power
- Watts, power factor, displacement power factor, VA and VAR.
- Voltage and current waveforms.
- New! Calculations 3-phase power on balanced loads from a
single-phase measurement.
|
| |
|
|
 |
Sags and Swells
|
| |
|
|

|
Transients
-
Catch voltage transients and waveform distortion.
-
See current at the instant of voltage events.
-
Catch and save up to 40 transients.
- Correlate the cause of distortion with time and date
stamps.
|
|
 |
| |
|
Menu Items |
Measurements |
Ranges |
Accuracy |
| Volts/Amps/Hz |
Volts
Amps
Mains frequency |
5.000 V-600 V RMS (AC & DC)
50.00 V-50.00 kA RMS (AC & DC)
40.0 to 70.0 Hz |
±(1%+10)
±(0.5%+2)
|
Power
|
Watts, VAR, VA,
PF, DPF |
250 W to 2.5MW
0.25 to 1.00 |
±(4%+4)
±0.04 |
Harmonics
|
Volts
Amps
Watts
K-factor |
1st to 51st harmonic
1st to 51st
1st to 51st
1.0 to 30.0 |
±(3%+2) to ±(15%+5)
±(3%+2) to ±(15%+5)
±(3%+2) to ±(30%+5)
±10% |
| Sags and Swells |
Voltage and Current |
4 minutes -16 days selectable |
±(2%+10) |
Transient Capture
|
40 ns pulse width
Up to 40 transients |
Select 20/50/100/200% above or
below line voltage |
±5% of full scale
|
| Inrush Current |
1 second to 5 minutes selectable |
1 Amp to 1000Amps |
±5% of full scale |
Ohms/Continuity/
Capacitance |
Ohms
Capacitance |
500.0Ω to
30.00MΩ
50.00 nF to 500.0µF |
±(0.6%+5)
±(0.2%+10) |
Temperature
(with accessory) |
°C
°F |
-100.0°C to
400.0°C
-200.0°F to 800.0°F |
±(0.5%+5)
±(0.5%+5) |
Scope
|
dc, ac, ac+dc, peak,
peak-peak, Hz, duty cycle,
phase, pulse width,
crest factor. |
Sampling rate: 25MS/sec
Bandwidth:
Voltage BW (Channel 1): 20MHz
Current BW (Channel 2): 15kHz |
|
| Screen saves |
All functions |
20 screens with data |
|
Recording
|
V/A/Hz, Power, Harmonics,
Ω/Cap, Temperature, Scope
|
4 min-16 days selectable
|
Select any two parameters in
each display mode. |
|
| |
| |
 |
| |
Battery Life
|
Rechargeable Ni-Cd pack (charger included), 4 hours
typical (continuous operation) |
| Shock and Vibration |
Mil 28800E, Type 3, Class III, Style B |
| Operating Temperature |
0 °C to 50°C (32°F to 122°F) |
| Case |
IP51 (dust, drip waterproof) |
| Dimensions |
232mm x 115mm x 50mm (9.1" x 4.5" x 2") |
| Weight |
1.1 kg (2.5lbs.) |
| Safety |
IEC 1010-1 CAT III-600V. Tested and approved to UL 3111-1,
CSA C.22.2 No. 1010.1-92 |
| Warranty |
Three Years on Instrument, One year on accessories |
|
| |
| |
 |
| |
| Model |
Description |
|
Fluke 43B
|
Power Quality Analyzer
Includes:
- C120 Hard Case.
- TP1 Flat-tipped Slim-Reach™ Test Probes.
- TP4 4 mm Round Slim-Reach™ Test Probes.
- i400s AC Current Clamp.
- OC4USB Optically Isolated USB Interface Adapter.
- BP120MH Rechargeable NiMH Battery Pack (installed).
- PM 8907 Line Voltage Adapter/Battery Charger.
- SW43W FlukeView™ Power Quality Analyzer Software and Users Manual on
CD-ROM.
- Shielded Banana-to-BNC Adapter.
- Users Manual / Application Guide.
- Power Quality CD-ROM.
|
 |
|
|