| Navigation:
Prova Instruments
>
Flexible Current Probe and Meter
>
AFLEX 6300 Graphic Analyzer |
| |
|
|
| |
Model AFLEX 6300
Flexible Graphic Power Quality Analyzer |
Flexible probe, different from normal clamp meters, can pass through
obstacles at will and wind many conducting wires simultaneously, maximum
diameter 170mm.
|

|
Features
- Power Quality Analysis for Single and Balanced Three Phase
Systems.
- True RMS measurement of voltage with 0.5% basic accuracy.
- True RMS measurement of current with 1% of range basic
accuracy.
- 3000Amp.
- Large LCD Display with Backlight.
- Graphic Waveform of Voltage and Current.
- Graphic Phasor Diagram.
- Active Power (KW), Apparent (KVA) and Reactive Power (KVAR).
- Power Factor and Phase Angle.
- Energy (WH, KWH, KVARH, PFH).
- Maximum Demand (MD in W, KW, MW) with Programmable Period.
- Harmonic Analysis Volts and Current to 50th Order.
- Display of 25 Harmonics on Screen.
|
|
- Display of waveform (512 Samples/Period), Data-logging of 32, 64,
128 or 256 Points/Cycles.
- Total Harmonic Distortion (%THD-F).
- Capture 128 Transient Events (Time + Cycles + Faults) with
Programmable Threshold (%), can also be Reviewed in LCD.
- Output of Waveform, Power Parameters and 50 Harmonics at Command.
- 50,000 Records with Programmable Interval (1 to 6000 seconds).
- Optical Isolated RS-232 Interface.
- Smart Data-logging to save Battery Power for Long-term Monitoring.
- Built-in Calendar Clock for Data-logging.
|
|
Specifications
|
(23°C
±5°C)
|
|
| AC Watt 50/60Hz, PF 0.5 to 1, CT=1 |
| Range |
Resolution |
Accuracy of Reading |
| 10.0 to 999.9W |
0.1 W |
2% of range |
| 1.000 to 9.999KW |
0.001KW |
2% of range |
| 10.00 to 99.99KW |
0.01KW |
2% of range |
| 100.0 to 999.9KW |
0.1KW |
2% of range |
| 1000 to 9999KW |
1KW |
2% of range |
|
| |
| |
| AC Current 50/60Hz, Auto Range, True-rms |
| Range |
Resolution |
Accuracy of
Readings |
| 0 to 300.0A |
0.1A |
±1% of range |
| 300.0 to 999.9A |
0.1A |
±1% of range |
| 1000 to 3000A |
1A |
±1% of range |
|
| |
| |
| AC Voltage 50/60Hz, Auto Range, True-rms |
| Range |
Resolution |
Accuracy of
Readings |
| 4.0V to 600.0V |
0.1V |
±0.5% ±5 digits |
|
| |
| |
| Harmonics of AC Voltage in % and Magnitude (1 to 50th
order) |
| Range |
Resolution |
Accuracy in Percentage |
Accuracy in Magnitude |
| 1 to 20th |
0.1% |
±2% |
±2% ±0.5V |
| 21 to 50th |
0.1% |
4% of reading ±2.0% |
4% of reading ±0.5% |
|
| |
| |
| Harmonics of AC Current in % and Magnitude (1 to 50th
order) |
| Range |
Resolution |
Accuracy in Percentage |
Accuracy in Magnitude |
| 1 to 20th |
0.1% |
±2% |
±2% of reading ±0.4A |
| 21 to 50th |
0.1% |
4% of reading ±2.0% |
4% of reading ±0.4A |
|
| |
| |
| Total Harmonic Distortion (%THD-F, 1 to 50th order) |
| Range |
Resolution |
Accuracy of Reading |
| 0.0 to 20% |
0.1% |
±2% |
| 20 to 100% |
0.1% |
±6% of reading ±1% |
| 100 to 999.9% |
0.1% |
±10% of reading ±1% |
|
| |
| |
|
General Specifications |
|
Probe Length: AFLEX 6300-24 |
24 inches (610mm) |
|
Minimum Bending Diameter |
35mm |
|
Probe Connector Diameter |
23mm |
|
Cable Probe Diameter |
14mm |
|
Cable Length/Probe to Inst. |
170mm |
|
Instrument Dimensions |
130mm (L) x 80mm (W) x 43mm (H) |
|
Battery |
Two 1.5V SUM-3 |
|
Display |
LCD 4 + 4 digits |
|
Range Selection |
Auto |
|
Temperature (Operating) |
-10°C to 85°C |
|
Humidity (Operating) |
15% to 85% RH |
|
Altitude |
2000 Meters |
|
Weight |
430g (battery included) |
|