Obiat Pty Ltd distributors of Electronic and Professional Scientific Test Equipment.

 

Sydney Australia

. . . . keeping your world up and running

Navigation: Prova Instruments > Flexible Current Probe and Meter  > AFLEX 6300 Graphic Analyzer
 
Prova Logo Flexible Current Probes and Meters
 
Model AFLEX 6300
Flexible Graphic Power Quality Analyzer

Flexible probe, different from normal clamp meters, can pass through obstacles at will and wind many conducting wires simultaneously, maximum diameter 170mm.
 
AFLEX 6300 Flexible Graphic Power Quality Analyzer

 

 

Features
  • Power Quality Analysis for Single and Balanced Three Phase Systems.
  • True RMS measurement of voltage with 0.5% basic accuracy.
  • True RMS measurement of current with 1% of range basic accuracy.
  • 3000Amp.
  • Large LCD Display with Backlight.
  • Graphic Waveform of Voltage and Current.
  • Graphic Phasor Diagram.
  • Active Power (KW), Apparent (KVA) and Reactive Power (KVAR).
  • Power Factor and Phase Angle.
  • Energy (WH, KWH, KVARH, PFH).
  • Maximum Demand (MD in W, KW, MW) with Programmable Period.
  • Harmonic Analysis Volts and Current to 50th Order.
  • Display of 25 Harmonics on Screen.
  • Display of waveform (512 Samples/Period), Data-logging of 32, 64, 128 or 256 Points/Cycles.
  • Total Harmonic Distortion (%THD-F).
  • Capture 128 Transient Events (Time + Cycles + Faults) with Programmable Threshold (%), can also be Reviewed in LCD.
  • Output of Waveform, Power Parameters and 50 Harmonics at Command.
  • 50,000 Records with Programmable Interval (1 to 6000 seconds).
  • Optical Isolated RS-232 Interface.
  • Smart Data-logging to save Battery Power for Long-term Monitoring.
  • Built-in Calendar Clock for Data-logging.
Specifications
 
(23°C ±5°C)
 
AC Watt 50/60Hz, PF 0.5 to 1, CT=1
Range Resolution Accuracy of Reading
10.0 to 999.9W 0.1 W 2% of range
1.000 to 9.999KW 0.001KW 2% of range
10.00 to 99.99KW 0.01KW 2% of range
100.0 to 999.9KW 0.1KW 2% of range
1000 to 9999KW 1KW 2% of range
 
 
AC Current 50/60Hz, Auto Range, True-rms
Range Resolution Accuracy of Readings
0 to 300.0A 0.1A ±1% of range
300.0 to 999.9A 0.1A ±1% of range
1000 to 3000A 1A ±1% of range
 
 
AC Voltage 50/60Hz, Auto Range, True-rms
Range Resolution Accuracy of Readings
4.0V to 600.0V 0.1V ±0.5% ±5 digits
 
 
Harmonics of AC Voltage in % and Magnitude (1 to 50th order)
Range Resolution Accuracy in Percentage Accuracy in Magnitude
1 to 20th 0.1% ±2% ±2% ±0.5V
21 to 50th 0.1% 4% of reading ±2.0% 4% of reading ±0.5%
 
 
Harmonics of AC Current in % and Magnitude (1 to 50th order)
Range Resolution Accuracy in Percentage Accuracy in Magnitude
1 to 20th 0.1% ±2% ±2% of reading ±0.4A
21 to 50th 0.1% 4% of reading ±2.0% 4% of reading ±0.4A
 
 
Total Harmonic Distortion (%THD-F, 1 to 50th order)
Range Resolution Accuracy of Reading
0.0 to 20% 0.1% ±2%
20 to 100% 0.1% ±6% of reading ±1%
100 to 999.9% 0.1% ±10% of reading ±1%
 
 

General Specifications

Probe Length: AFLEX 6300-24

24 inches (610mm)

Minimum Bending Diameter

35mm

Probe Connector Diameter

23mm

Cable Probe Diameter

14mm

Cable Length/Probe to Inst.

170mm

Instrument Dimensions

130mm (L) x 80mm (W) x 43mm (H)

Battery

Two 1.5V SUM-3

Display

LCD 4 + 4 digits

Range Selection

Auto

Temperature (Operating)

-10°C to 85°C

Humidity (Operating)

15% to 85% RH

Altitude

2000 Meters

Weight

430g (battery included)

 

AEMC | AMPROBE | CIE | FLUKE | HT ITALIA | HODEN | PROVA | POMONA | RAYTECH |  SILVERTRONIC
Home | PRODUCTS | SEARCH
Obiat Pty. Ltd.
A.C.N. 003 166 952      A.B.N. 23 003 166 952
Unit 9A/8 Avenue of the Americas, Newington NSW 2127 Australia
P.O. Box 6901 Silverwater  NSW Australia 1811

Phone: 61-2-9748- 8699

Fax: 61-2-9748-8544

E-mail:
 

 information@obiat.com.au
sales@obiat.com.au

Copyright ©                                             Last Update: Sunday, 01 May 2011