The TR-Mark II R is the 19" Rack
Mount version of the legendary TR-Series which has quickly become
recognized as the World's most advanced Three Phase Transformer
Ratiometer.
The TR-Mark II R fully automatic measures
Turns Ratio, Voltage Ratio, Excitation Current, Phase
Relationship, and Phase Displacement.
A single hook-up to the transformer is all that
is needed to run a complete series of tests because all
connections of various transformer configurations are accomplished
internally.
The Mark II R system does not require any
charts or calculations for testing. The system can test more
combinations of transformer configurations than any other system
making it the most versatile and easiest to use system
available.
The Mark II R tests one of the widest
ratio ranges available (0.8....13,000) and has the highest
accuracy of any Automatic Three Phase Ratiometer (0.08%).
|
|

|

- Fully Automatic.
- Highest accuracy of measurements of Voltage/Turns Ratio, Current and
Phase displacement.
- Ability to switch between voltage ratio and turns ratio.
- Large internal storage for test results.
- Conforms to IEC, ANSI and Australian Standards.
- Single hookup to the transformer.
- Single push button operation.
- Five test voltage ranges: 1V, 10V, 40V, 100V and
Automatic.
- Comparison with a nominal ratio.
- Load on test object < 0.05VA.
- Enhanced, heavy duty protection circuitry.
- Safety emergency shut off.
- Centronics (Parallel) and RS-232 (Serial) Interface.
- Self Calibrating.
- Available output for tap changer application.
- PC application for data transfer.
- Firmware up-date available via the internet..
- 5-year standard warranty.
|
 |
| Range Base |
With 100V and 40V |
With 10V |
Resolution |
| 0.8 to 2,000 |
±0.08% |
±0.15% |
5 digits
(all ranges) |
| 2,001 to 4,000 |
±0.1% |
±0.22% |
| 4,001 to 13,000 |
±0.3% |
±0.5% |
|
|
|
|
|
 |
| Turns Ratio Range |
0.8 to 13,000 |
| Test Current |
0 to 1 ampere, Accuracy 0.001 |
| Phase Angle |
±180 Degrees, Accuracy 0.05 degree |
| Operating Temperature |
-10°C to 60°C |
| Storage Temperature |
-40°C to 70°C |
| Test Voltage |
User Selectable: 100V, 40V, 10V and 1V AC 1 Ampere |
| Panel Display |
LCD Graphic with backlight |
| Front Panel |
Sealed, Piezo-electric actuation |
| Interface |
9 pin RS-232 (Serial) / 25 pin Centronics (Parallel) |
| Memory Storage |
Internal storage for more than 100 complete transformers |
|
|
|
|
|
 |
| Power Source |
100V to 250V AC 50Hz/60Hz Autoranging; Fuse: 2 Amp |
| Dimensions |
482.6mm (L) x 371mm (W) x 132.6mm (H) |
| Weight |
7.3 kg |
|
|
|
|
|
 |
| Tools or Toolbox |
Free download of application Tools or Toolbox |
| Model TR0201 |
Measuring cable extensions 20 meters |
| Model TR0203 |
External Trigger |
| Extended Warranty |
Annual Warranty Extension |
|
|
|
|
|
 |
| Model TR-Mark II R |
TR-Mark II Automatic Three Phase Ratiometer
Rackmount (3U) |
|
|
|
|